10 kV变电站电磁辐射特性及对周边设备影响分析

Analysis of electromagnetic radiation characteristics of 10 kV substation and its influence on surrounding equipment

  • 摘要: 为研究建筑物内10 kV变电站运行过程中周围电磁辐射特性及对敏感设备的影响,选取某建筑物内10 kV变电站为研究对象,搭建了实验测试系统,分析了建筑物内外10 kV变电站电磁辐射信号特性,进一步研究了标准未规定的变电站电磁辐射对敏感设备工作状态和电源线传导测试试验结果的影响,研究结果表明:在1.2 kHz频率以下的低频范围内变电站房间内电磁场强度明显大于房间周边电磁场强度,在1.2 kHz~50 GHz频段范围内,变电站房间周边电场强度与空旷环境电场强度基本相当;信号源和示波器、天线和频谱仪及精密时间分析仪在变电站内和周边工作正常;被试某型电台放置于变电站房间内部,电台临界工作状态信号强度值分别增加10 dBm、5 dBm;对处于临界工作状态下的某型电台电源线开展100~400 MHz电源线传导安全裕度试验,电台工作正常。

     

    Abstract:
    Background With the acceleration of urbanization and the upgrading and renovation of distribution networks, small 10 kV substations (including box-type and outdoor compact substations), as core terminal power supply facilities, have been widely deployed in densely populated areas such as residential quarters, commercial blocks and schools. Their spatial overlap with the daily life of the public is far greater than that of high-voltage substations.
    Purpose To study the electromagnetic radiation characteristics around a 10 kV substation in a building during operation and its impacts on sensitive equipment,
    Methods a 10 kV substation in a specific building was selected as the research object. An experimental testing system was established to analyze the electromagnetic radiation signal characteristics of the 10 kV substation, this paper further studies the impacts of substation electromagnetic radiation on the operating status of sensitive equipment and power-line conducted test results, which not specified in existing standards.
    Results The results show that: within the low-frequency range below 1.2 kHz, the electromagnetic field intensity inside the substation room is significantly higher than that in surrounding areas. In the 1.2 kHz -50 GHz frequency band, the electric field intensity around the substation room is basically equivalent to that in an open environment. Signal sources and oscilloscopes, antennas and spectrum analyzers, and precision time analyzers placed inside and around the substation operated normally. When an injection communication radio was placed inside the substation room, the critical operating signal strength values of the tested radio increased by 10 dBm and 5 dBm respectively. Conducted a power line conduction safety margin test in the range of 100 MHz to 400 MHz on the power line of the communication radio station under the critical working state, and the radio station operates normally.
    Conclusions The electric field strength around the substation room is basically equivalent to that in an open environment. Conventional test instruments and precision time analyzers work normally when placed inside and around the substation. The signal strength value of the tested radio station under the critical operating state increases. The electromagnetic radiation inside the substation does not affect the test results of the conducted safety margin. The research results can provide a scientific basis for site selection optimization of small 10 kV substations and the layout of sensitive equipment in the surrounding area.

     

/