Abstract:
Background With the acceleration of urbanization and the upgrading and renovation of distribution networks, small 10 kV substations (including box-type and outdoor compact substations), as core terminal power supply facilities, have been widely deployed in densely populated areas such as residential quarters, commercial blocks and schools. Their spatial overlap with the daily life of the public is far greater than that of high-voltage substations.
Purpose To study the electromagnetic radiation characteristics around a 10 kV substation in a building during operation and its impacts on sensitive equipment,
Methods a 10 kV substation in a specific building was selected as the research object. An experimental testing system was established to analyze the electromagnetic radiation signal characteristics of the 10 kV substation, this paper further studies the impacts of substation electromagnetic radiation on the operating status of sensitive equipment and power-line conducted test results, which not specified in existing standards.
Results The results show that: within the low-frequency range below 1.2 kHz, the electromagnetic field intensity inside the substation room is significantly higher than that in surrounding areas. In the 1.2 kHz -50 GHz frequency band, the electric field intensity around the substation room is basically equivalent to that in an open environment. Signal sources and oscilloscopes, antennas and spectrum analyzers, and precision time analyzers placed inside and around the substation operated normally. When an injection communication radio was placed inside the substation room, the critical operating signal strength values of the tested radio increased by 10 dBm and 5 dBm respectively. Conducted a power line conduction safety margin test in the range of 100 MHz to 400 MHz on the power line of the communication radio station under the critical working state, and the radio station operates normally.
Conclusions The electric field strength around the substation room is basically equivalent to that in an open environment. Conventional test instruments and precision time analyzers work normally when placed inside and around the substation. The signal strength value of the tested radio station under the critical operating state increases. The electromagnetic radiation inside the substation does not affect the test results of the conducted safety margin. The research results can provide a scientific basis for site selection optimization of small 10 kV substations and the layout of sensitive equipment in the surrounding area.